Page 30: Setting up the hardware
3-2
Setting Up RS-232 Point-to-Point Serial Communications
Hardware
Required Hardware
The following hardware is required for an RS-232 serial connection:
Setting Up the Hardware
To use DriveTools32 with this type of communications, you must:
•
Ensure that the drive and adapter are properly installed and powered.
•
Ensure that cables are securely connected and protected from damage.
•
Use a standard straight-thru serial cable to connect your computer to the
adapter.
•
Ensure that your serial communications module settings are correct. In most
cases, you should use the factory-set defaults. If you decide to change the
default settings, note the new settings because you need to know them when
you configure RSLinx and DriveTools32. Refer to the appropriate manual:
Important: If you are using a 1203-GD2 serial communications module, its
firmware must be release 2.04 or greater. If you use an earlier version, all
parameters may not be shown.
Drive
Required Drive Hardware
Required Computer
Hardware
SCANport-Compatible
➀
Serial Adapter(1203-SSS, 1203-GD2,
1203-GK2, or 1336-GM2) and appropriate
cable(s)
RS-232 port
160 SSC
160-RS1 Serial Adapter and appropriate cable
RS-232 port
➀
For a list of SCANport-compatible products, refer to Appendix A, Products Supported by DriveTools32.
Communications Module
Refer To:
1203-GD2, 1203-GK2, or 1336 GM2
Bulletin 1203 Serial Communications Module User Manual
1203-SSS
Smart Self-powered Serial Converter User Manual