Introduction, Module input image, Appendix b – Rockwell Automation 1769-IF16V Compact High Density Analog Input Modules User Manual
Page 63: Introduction module input image, I:3.17/2, Appendix
Publication 1769-UM018A-EN-P - October 2008
63
Appendix
B
Module Addressing and Configuration with
MicroLogix 1500 Controller
Introduction
This appendix examines the modules’ addressing scheme and
describes module configuration using RSLogix 500 software and a
MicroLogix 1500 controller.
Module Input Image
The modules’ input image file represents data words and status bits.
Input words 0…15 hold the input data that represents the value of the
analog inputs for channels 0…15. These data words are valid only
when the channel is enabled and there are no errors. Input words
17…21 hold the status bits. To receive valid status information, the
channel must be enabled.
For example, to obtain the general status of channel 2 of the analog
module located in slot 3, use address I:3.17/2.
Topic
Page
Configure Analog I/O Modules in a MicroLogix 1500 System
TIP
The end cap does not use a slot address.
I:3.17/2
Input File Type
Slot
Word
Bit
Bit Delimiter
Word Delimiter
Element Delimiter