Physical specifications, Environmental specifications – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual
Page 98
Publication 1746-UM007C-EN-P - July 2004
A-2 Specifications
Physical Specifications
Environmental
Specifications
Specification
Value
LED Indicators
5, green status indicators, one for each of 4 channels
and one for module status
Module ID Code
3510
Recommended Cable:
For Thermocouple inputs
Appropriate shielded twisted pair thermocouple
extension wire
(1)
(1) Refer to the thermocouple manufacturer for the correct extension wire.
For mV inputs
Belden #8761 or equivalent
Maximum Wire Size
Two 14 AWG wires per terminal
Maximum Cable Impedance
25
ohms maximum loop impedance, for <1LSB error
Terminal Block
Removable, Allen-Bradley spare part Catalog Number
1746-RT32
Specification
Value
Operating Temperature
(1)
(1) When the NT4 module detects 0°C (32°F) [(+/- 3°C) +/- 5.4°F] at the CJC, it will detect an out-of-range condition
and set values to downscale -270°C (-454°F). It is recommended that ambient temperature surrounding the SLC
500 system be maintained above 3°C (37.4°F) in order for the NT4 module to measure temperature correctly
without detecting an out-of-range condition.
0°C to 60°C (32°F to 140°F)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Relative Humidity
5% to 95% (without condensation)
Certification
Marked for all applicable directives
CSA approved
C-UL Listed Industrial Control Equipment
for use in Class 1, Div 2 Hazardous
Locations