Channel configuration -5, Channel configuration – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual
Page 91

Publication 1746-UM007C-EN-P - July 2004
Application Examples 8-5
Channel Configuration
Configuration setup for ambient thermocouple:
•
channel 0
•
type T thermocouple
•
display temperature to tenths of a degree
•
zero data word in the event of an open circuit
•
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for bath thermocouple:
•
channel 1
•
type J thermocouple
•
display temperature to tenths of a degree
•
zero data word in the event of an open circuit
•
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for steam thermocouple:
•
channel 2
•
type K thermocouple
•
display temperature to tenths of a degree
•
zero data word in the event of an open circuit
•
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for chilled H2O thermocouple:
•
channel 3
•
type J thermocouple
•
display temperature to tenths of a degree
•
zero data word in the event of an open circuit
•
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for cabinet temperature:
•
channel 0
•
CJC temperature
•
display temperature to tenths of a degree
•
zero data word in the event of an open circuit
•
60 Hz input filter to provide 60 Hz line noise rejection