beautypg.com

Data table, Program listing – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 89

background image

Publication 1746-UM007C-EN-P - July 2004

Application Examples 8-3

Program Listing

15

Rung 2.0

First Pass Bit

] [

S:1

MOVE
Source N10:0

Dest

O:3.0

Initialize Channel 0
of NT4

MOV

Rung 2.1

Convert the channel 0 data word (degrees F) to BCD and write this to the LED display

.

If channel 0 is ever disabled, a zero is written to the display.

.

TO BCD
Source

I:3.0

Dest

N7:0

TOD

MASKED MOVE
Source

N7:0

Mask

0FFF

Dest

O:2.0

MVM

Rung 2.2

END

The use of the masked move instruction with the 0FFF mask allows you to use outputs 12, 13,
14, and 15 for other output devices in your system. The 7-segment display uses outputs 0-11.

.

Data Table

address 15 data 0 address 15 data 0

N10:0 0000 1001 0001 0000

This manual is related to the following products: