Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual
Page 100
Publication 1746-UM007C-EN-P - July 2004
A-4 Specifications
1746-NT4 Module Accuracy
Input Resolution per
Thermocouple Type at Each
Filter Frequency
Input Type
With Autocalibration
(1)
(1) Assumes the module terminal block temperature is stable.
Without Autocalibration
Maximum Error
@ 25°C
Maximum Error
@ 77°F
Temperature Drift
(0°C-60°C)
J
±1.06°C
±1.91°F
±0.0193°C/°C, °F/°F
K
±1.72°C
±3.10°F
±0.0328°C/°C, °F/°F
T
±1.43°C
±2.57°F
±0.0202°C/°C, °F/°F
E
±0.72°C
±1.3°F
±0.0190°C/°C, °F/°F
S
±3.61°C
±6.5°F
±0.0530°C/°C, °F/°F
R
±3.59°C
±6.46°F
±0.0530°C/°C, °F/°F
B
±3.12°C
±5.62°F
±0.0457°C/°C, °F/°F
N
±1.39°C
±2.5°F
±0.0260°C/°C, °F/°F
±50 mV
±50 mV
±50 mV
±1.0 mV/°C, ±1.8 mV/°F
±100 mV
±50 mV
±50 mV
±1.5 mV/°C, ±2.7 mV/°F
0.0
0.2
0.4
0.6
0.8
300
150
0
150
300
450
600
750
900
1050
1200
( C)
508
238
32
302
572
842
1112
1382
1652
1922
2192
0.36
0.72
1.08
1.44
( F)
Temperature
( C)
( F)
Resolution
250 Hz
50/60 Hz
10 Hz
0.72
1.44
2.16
2.88
5.76
11.52
17.28
23.04
0.40
0.80
1.20
1.60
3.20
6.40
9.60
12.80
Type E Thermocouple
˚
˚
˚
˚
_
_
_
_