Add-on instructions external access considerations – Rockwell Automation Logix5000 Controllers I/O and Tag Data Programming Manual User Manual

Page 73

background image

Data access control

Chapter 4

• If the member’s data type is User-defined and the child-member has a

different external access level from its parent, the more restrictive external

access level applies to the child-members.

The following table describes the conditions in which the External Access
column is unavailable.

To pick

Considerations

Change existing

data type

The External Access column is unavailable if:
• You do not have permission to change the external access settings

(2)

.

• The redundancy controller is in any state that does not allow changes.
• The data type is applied to tags and the controller is online.
Tip: Data type size is not affected by the external access attribute.

Predefined, module-defined,

Strings type

The External Access column is always visible but unavailable. The Set External Access

entry is added to the bottom of the row header context menu, but it is always unavailable.

(2) If you have User-defined Data Type Modify permission, you also can modify external access of a User-defined data type.

You can use external access settings with parameters and local tags of Add-On

Instructions. For example, if you define an input parameter with external access of

read only, the member that represents that parameter in the Add-On Instruction

data type cannot be written.

The following table describes the external access options for various Add-On
Instruction parameters and tags.

Add-0n Instruction Parameters and Tags

External Access Options

Local tag

Read/Write
Read Only
None

Input parameter

Output parameter
EnableIn parameter

Read Only

EnableOut parameter

InOut parameter

Not Applicable

You can choose the external access for an Add-On Instruction tag from the list on

the New Add-On Instruction Parameter or Local Tag dialog box or from the
External Access column on the Tag Editor.

Add-on instructions

external access

considerations

Rock well Automati on Publication 1756- PM004E -EN-P - October 2014

73