Chapter 1

Communicate with I/O modules

Ownership

In a Logix5000 system, modules multicast data. This means that multiple devices

can receive the same data at the same time from a single device.

When you choose a communication format, you have to choose whether to

establish an owner or listen-only relationship with the module.

Term

Definition

Owner controller

The controller that creates the primary configuration and communication connection to a module. The owner

controller writes configuration data and can establish a connection to the module.

An owner connection is any connection that does not include Listen-Only in its Comm Format.

Listen-only connection

An I/O connection where another controller owns/provides the configuration data for the I/O module. A controller

using a listen-only connection only monitors the module. It does not write configuration data and can only maintain a

connection to the I/O module when the owner controller is actively controlling the I/O module.

Use the following table to choose the type of ownership for a module.

If module is

And another controller

And you want to

Then use this type of connection

Input module

Does not own the module

------------------------------------>

Owner (not listen-only)

Owns the module

Maintain communication with the module if it loses

communication with the other controller

Owner (not listen-only)

Use the same configuration as the other owner

controller.

Stop communication with the module if it loses

communication with the other controller

Listen-only

Output module

Does not own the module

------------------------------------>

Owner (such as, not listen-only)