Force I/O

Chapter 3

Force an input value

Forcing an input or consumed tag:

• Overrides the value regardless of the value of the physical device or

produced tag.

• Does not affect the value received by other controllers monitoring that

input or produced tag.

Force an output value

Forcing an output or produced tag overrides the logic for the physical device or

other controller. Other controllers monitoring that output module in a listen-only

capacity also see the forced value.

To override an input value, output value, produced tag, or consumed tag, use an

I/O force.

ATTENTION: Forcing can cause unexpected machine motion that could injure personnel. Before you use a force,

determine how the force affects your machine or process and keep personnel away from the machine area.

− Enabling I/O forces causes input, output, produced, or consumed values to change.
− If forces are enabled and you install a force, the new force immediately takes effect.

1. Check the state of the I/O Forces status indicator.

If

Then note

Off

No I/O forces currently exist.

Flashing

No I/O forces are active. But at least one force already exists in your project. When you enable I/O
forces, all existing I/O forces also take effect.

Solid

I/O forces are enabled (active). When you install (add) a force, it immediately takes effect.

2. Open the routine that contains the tag that you want to force.

3. Right-click the tag and then click Monitor.

If necessary, expand the tag to show the value that you want to force (that is,
BOOL value of a DINT tag).

4. Install the force value.

Add an I/O force