Add the Switch to Software
Appendix E
Add-on Profile
To add the switch to RSLogix 5000 software, version 15.02.00 or later, or the
Logix Designer application, version 21.00.00 or later, by using the Add-on Profile
(AOP), follow this procedure.
1. Locate the module AOP
2. Check the installation documentation included with the Add-on Profile to
determine the required firmware revision for the 1783-EMS switch.
• If you do not have the minimum revision of 1783-EMS firmware,
upgrade your switch before proceeding. Refer to
for more
information about the upgrade procedure for the 1783-EMS switch.
• To obtain the latest firmware, check the 1783-EMS website or contact
Technical Support.
3. Install the Add-on Profile.
4. Add the 1783-EMS switch to the software using this procedure.
a. Right-click your Logix Ethernet card under the I/O configuration tree
and choose New Module.
b. Click the Communications tab.
c. Choose the 1783-EMS switch from the list.
d. Give the switch a name in your program and enter its IP address.
e. Click OK.
IMPORTANT
You need a Rockwell Automation MySupport account to download the
AOP. If you do not have one, follow the steps on the MySupport website
to obtain an account.
IMPORTANT
You must install the Add-on Profile for the switch before using the
switch in the Logix programming environment.