2. From the Mirroring Configuration pull-down menu, choose Enabled.
3. In the Mirror From column, specify the traffic to capture and send to a
destination port for analysis.
• To monitor incoming traffic for a port, check the In checkbox next to
the port number.
• To monitor outgoing traffic for a port, check the Out checkbox next to
the port number.
• To monitor both incoming and outgoing for a port, check the In and
Out checkboxes next to the port number.
• If you do not want to monitor traffic for a port, leave both checkboxes
cleared. This is the default configuration.
4. In the Capture To column, click the option button next to the port
number to which to send captured traffic.
5. Configure optional input and output mirror filters.
Options include the following:
• All transmitted
• All transmitted frames with the destination address specified in the
MAC field
• All received frames with the source address specified in the MAC field
6. Specify input and output dividers for further filtering.
7. Click Apply Changes.
EXAMPLE
Port 4 is set up to capture incoming frames from port 3. The input filter is set up
to capture traffic with source address 00:00:BC:03:4E:08. The input divider is
set to 2 to capture every other frame coming to port 3 with a source address of
00:00:BC:03:4E:08. This MAC address belongs to IP address 100.100.101.2.