A - upgrade firmware, Upgrade with the web management interface, Appendix a – Rockwell Automation 1783-EMS08T Stratix 6000 Ethernet Managed Switch User Manual User Manual
Page 67: Upgrade firmware, Appendix

Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
67
Appendix
A
Upgrade Firmware
This appendix provides information about how to upgrade 1783-EMS firmware.
Upgrade with the Web
Management Interface
Use this procedure to upgrade the 1783-EMS switch by using the web interface.
For information about how to access the web interface for the switch, refer to
.
1. From the navigation pane, expand the Diagnostics folder and click
Firmware Upgrade.
2. Click Browse and select the firmware (boot.img) file.
3. Click Upgrade.
4. Enter the user name and password.
By default, the user name is 'uploader' (lowercase) and the password is
'PASSWORD' (all caps). Change the user name and password by selecting
Basic Configuration and Set Security from the web interface of the 1783-
EMS switch.
5. Check the firmware revision when the upgrade is complete to make sure
the upgrade was successful.
6. Repeat this procedure to upgrade the web browser (webdata.img) and the
embedded manual (qsdata.img) files.
WARNING: The 1783-EMS switch cycles power automatically at the end
of the upgrade procedure. Any switching activity is temporarily
interrupted.