beautypg.com

Rockwell Automation 1794-IT8,D17946.5.7 Thermocouple/Millivolt Input Module User Manual

Page 63

background image

Specifications

A–9

Publication 1794-6.5.7 – March 1997

Template revised June 23, 1995

Error Due to Open Circuit Current Through Loop Resistance

Input Type

Error per Ohm of Loop Resistance

B

0.091

o

C

0.164

o

F

E

0.013

o

C

0.023

o

F

J

0.016

o

C

0.029

o

F

K

0.024

o

C

0.043

o

F

R

0.076

o

C

0.137

o

F

S

0.083

o

C

0.149

o

F

T

0.022

o

C

0.040

o

F

N

0.028

o

C

0.050

o

F

C

0.055

o

C

0.099

o

F

L

0.015

o

C

0.028

o

F

mV

0.417

µ

V (2.4

= 1 LSB of error)

Worst Case Repeatability for the Thermocouple/mV Input Module

Input Type

Repeatability with Filter

(o

C) (

o

F)

Repeatability without Filter

(

o

C) (

o

F)

B

+1.00

o

C

+1.80

o

F

+2.00

o

C/

o

C

+3.60

o

F/

o

F

E

+0.16

o

C

+0.29

o

F

+0.32

o

C/

o

C

+0.58

o

F/

o

F

J

+0.20

o

C

+0.36

o

F

+0.40

o

C/

o

C

+0.72

o

F/

o

F

K

+0.28

o

C

+0.50

o

F

+0.56

o

C/

o

C

+1.00

o

F/

o

F

R

+1.10

o

C

+1.98

o

F

+2.20

o

C/

o

C

+3.96

o

F/

o

F

S

+1.00

o

C

+1.80

o

F

+2.00

o

C/

o

C

+3.60

o

F/

o

F

T

+0.27

o

C

+0.54

o

F

+0.54

o

C/

o

C

+1.08

o

F/

o

F

N

+0.34

o

C

+0.61

o

F

+0.68

o

C/

o

C

+01.22

o

F/

o

F

C

+0.13

o

C

+0.23

o

F

+0.26

o

C/

o

C

+0.46

o

F/

o

F

L

+0.19

o

C

+0.30

o

F

+0.37

o

C/

o

C

+0.62

o

F/

o

F

mV

+12

µ

V

+12

µ

V

+24

µ

V/

o

C

+24

µ

V/

o

F

Note: The filter is enabled by setting bit 02 in write word 0.