Calibrating Your Module

Publication 1794-6.5.7 – April 1997

Read/Write Words for Calibration

Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 10

0

0

0

0

0

Bad

Cal

Cal

Done

Cal

Range

0

Diagnostic Status

Pwr

Up

Bad

Struct

CJC
over

CJC

Under

Write Word 0

8-Bit Calibration Mask

Cal
Clk

Cal hi
Cal lo

Filter Cutoff

FDF

Data Type

Offset Calibration

Inputs can be calibrated one at a time or all at once. To calibrate the
offsets for all inputs at once, proceed as follows:

1. Apply power to the module for 40 minutes before calibrating.

2. Connect 0.000V across each input channel. Connect all high

signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.

3. After the connections stabilize, use a block transfer write to set

the bit(s) in the calibration mask that correspond to the channel(s)
you want to calibrate to 1. (Bits 08 through 15 in write word 0.)

4. Send another block transfer write to set the cal-clk bit (07 in write

word 0) to 1.

5. Monitor the cal-done bit (09 in read word 10). If the calibration is

successful, the cal-done bit will be set to 1. Verify that the bad-cal
bit (10 in read word 10) and the cal-range bit (08 in read word 10)
are not set (0).

6. Send another block transfer write to set the cal-clk bit (07 in write

word 0) to 0.

7. Monitor the cal-done bit (09 in read word 10). The cal-done bit

will be reset to 0.

8. If the calibration is successful, proceed to the gain calibration.