How to Install Your Thermocouple/mV Input Module

Publication 1794-6.5.7

Methods of wiring the terminal base units are shown in the
illustration below.

Wiring the Terminal Base Units (1794-TB2 and -TB3 shown)

Wiring when total current draw is less than 10A

Wiring when total current draw is greater than 10A

Daisy-chaining

Individual

Total current draw through any base unit must not be greater than 10A

Combination

24V dc

24V dc

24V dc

24V dc

24V dc or
120V ac

24V dc

ATTENTION: Do not daisy chain power or
ground from the thermocouple terminal base unit to
any ac or dc discrete module terminal base unit.

!

Note: Use this configuration if using any
“noisy” dc discrete I/O modules in your system.

Thermocouple module wiring separate from discrete wiring.

Thermocouple

or Analog Module

Note: All modules powered by the same power supply
must be analog modules for this configuration.

Note: All modules must be analog modules for this configuration.

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Discrete

Module

Discrete

Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Discrete

Module

Discrete

Module