5–5

How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter

Publication 1794-6.5.7 – April 1997

Description

Decimal Bit

(Octal Bit)

Word

Read Word 11
continu

03 (03)

Powerup bit – this bit is set (1) until configuration data is received by the module.

continued

04–06 (04–06)

Critical Fault bits – If these bits are anything other than zero, return the module to the factory for repair.

07 (07)

Unused – set to 0

08 (10)

Calibration Range bit – set to 1 if a reference signal is out of range during calibration

09 (11)

Calibration Done bit – set to 1 after an initiated calibration cycle is complete.

10 (12)

Calibration Bad bit – set to 1 if the channel has not had a valid calibration.

11–15 (13–17)

Unused – set to 0

Write Word 1

00–01 (00–01)

Module Data Type

Bit

01

00

Definition

0

0

o

C (default)

0

1

o

F

1

0

Bipolar counts scaled between –32768 and +32767

1

1

Unipolar counts scaled between 0 and 65535

Bit 02 (02)

Fixed Digital Filter – When this bit is set (1), a software digital filter is enabled. This filter settles to
100% of a Full Scale step input in 60 times the selected first notch filter time shown on page 4–3.
Default – filter disabled.

03–05 (03–05)

A/D Filter First Notch Frequency

Bit

05

04

03

Definition

0

0

0

10Hz (default)

0

0

1

25Hz

0

1

0

50Hz

0

1

1

60Hz

1

0

0

100Hz

1

0

1

250Hz

1

1

0

500Hz

1

1

1

1000hZ

06 (06)

Calibration High/Low bit – This bit is set during gain calibration; reset during offset calibration.

07 (07)

Calibration clock – this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.

08–15 (10–17)

Calibration mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8
corresponds to channel 0, bit 9 to channel 1, and so on.