Calibrating Your Module

Publication 1794-6.5.7 – April 1997

Gain Calibration

After completing the offset calibration, proceed with the gain
calibration.

1. Apply power to the module for 40 minutes before calibrating.

2. Connect 75.000mV across each input channel. Connect all high

signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.

3. After the connections stabilize, send a block transfer write to the

module to set the bit in the calibration mask that corresponds to
the channel to be calibrated to 1, and the hi/lo bit (bit 06 in write
word 0) to 1. (Set bits 08 through 15 in write word 0 if calibrating
all inputs at one time.)

4. Send another block transfer write to set the cal-clk bit (07 in write

word 0) to 1.

5. Monitor the cal-done bit (09 in read word 10). If the calibration is

successful, the cal-done bit will be set to 1. Verify that the bad-cal
bit (10 in read word 10) and the cal-range bit (08 in read word 10)
are not set (0).

6. Send another BTW to set the cal-clk bit (07 in write word 0) to 0.

7. Send another BTW to set the hi/lo bit (bit 06 in write word 0)

to 0.

8. Monitor the cal-done bit (09 in read word 10). The cal-done bit

will be reset to 0.

9. If individually calibrating channels, repeat steps 1 through 7 for

offset calibration on any additonal channels you want to calibrate.

10.Send a block transfer write to the module to clear all calibration

mask bits to 0.