Calibrating Your Module

Publication 1794-6.5.7 – April 1997

Flow Chart for Calibration Procedure

Apply reference signal for offset

calibration to each channel to

be calibrated.

Set corresponding bits in the
calibration mask and set cal

Hi/Lo = 0

Set cal–clk =1

Set cal–clk =0

Cal–done = 1

?

NO

YES

NO

YES

Apply reference signal for gain

calibration to each channel to

be calibrated.

Retain corresponding bits in
the calibration mask and set

cal Hi/Lo = 1

Set cal–clk =1

Set cal–clk =0

and

cal hi/lo = 0

NO

YES

NO

YES

Clear corresponding bits in

the calibration mask

BTR

Legend:

Cal–done = 0

?

Cal–done = 0

?

Cal–done = 1

?

BTW

BTW

BTR

BTW

BTW

BTR

BTW

BTR

BTW

BTW

BTR

BTW = block transfer write

= block transfer read

Bad–cal = 0

?

NO

YES

Exit

Cal–range = 0

Bad–cal = 0

?

NO

YES

Exit

Cal–range = 0