beautypg.com

Rockwell Automation 1794-IT8,D17946.5.7 Thermocouple/Millivolt Input Module User Manual

Page 56

background image

Specifications

A–2

Publication 1794-6.5.7 – March 1997

Specifications

1

– 1794-IT8 Thermocouple/mV Input Module

Thermal Dissipation

Maximum 10.2 BTU/hr @ 31.2V dc

Keyswitch Position

3

General Specifications

External dc Power

Supply Voltage
Voltage Range

Supply Current

24V dc nominal
19.2 to 31.2V dc (includes 5% ac ripple)
19.2V dc for ambient temperatures less than 55

o

C

24V dc for ambient temperatures less than 55

o

C

31.2V dc for ambient temperatures less than 40

o

C

See derating curve.
150mA @ 24V dc

Cabling

Thermocouples inputs
Millivolt inputs

Appropriate shielded thermocouple extension wire

3

Belden 8761

Dimensions

Inches
(Millimeters)

1.8H x 3.7W x 2.1D
(45.7 x 94.0 x 53.3)

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity

Shock

Operating
Non-operating

Vibration

0 to 55

o

C (32 to 131

o

F) See derating curve.

–40 to 85

o

C (–40 to 185

o

F)

5 to 95% noncondensing (operating)
5 to 80% noncondensing (nonoperating)
30 g peak acceleration, 11(+1)ms pulse width
50 g peak acceleration, 11(+1)ms pulse width
Tested 5 g @ 10–500Hz per IEC 68-2-6

Agency Certification
(when product or packaging is marked)

CSA certified

CSA Class I, Division 2
Groups A, B, C, D certified

UL listed

CE marked for all applicable directives

Installation Instructions

Publication 1794-5.21

1

Specifications based on A/D filter first notch frequency of 10Hz

.

2

Use 1794-TB2 or -TB3 terminal base unit for millivolt inputs only. You must use a 1794-TB3T terminal base unit when using
thermocouple inputs.

3

Refer to the thermocouple manufacturer for the correct extension wire.