2–8

How to Install Your Thermocouple/mV Input Module

Publication 1794-6.5.7

The thermocouple/mV module has one status indicator that is on
when power is applied to the module. This indicator has 3 different
states:

A

B

A = Status Indicator – indicates diagnostic results and configuration status

B = Insertable label for writing individual input designations

INPUT 0

INPUT 2

INPUT 4

INPUT 6

INPUT 1

INPUT 3

INPUT 5

INPUT 7

THERMOCOUPLE INPUT 8 CHANNEL

3

1794–IT8

Allen-Bradley

+

+

+

+

+

+

+

+

OK

Color

State

Meaning

Red

On

Indicates a critical fault (diagnostic failure, etc.)

Blinking

Indicates a noncritical fault (such as open sensor, input out of range, etc.)

Green

On

Module is configured and fully operational

Blinking

Module is functional but not configured

Off

Module not powered

In this chapter, you learned how to install your thermocouple/mV
module in an existing programmable controller system and how to
wire to the terminal base units.

Module Indicators