Calibration setups, Wiring connections for the thermocouple module, Using a precision voltage source – Rockwell Automation 1794-IT8,D17946.5.7 Thermocouple/Millivolt Input Module User Manual

Page 47

background image

6–5

Calibrating Your Module

Publication 1794-6.5.7 – April 1997

Calibration Setups

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

9

10

11

12

13 14

15

0

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

34

1794-TB2, -TB3

0 –15

34–51

16–33

A

B

C

Precision Voltage Source

Using a Precision Voltage Source

CJC

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

9

10

11

12

13 14

15

0

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

34

1794-TB3T

0 –15

34–51

16–33

A

B

C

Precision Voltage Source

CJC

CJC

Note 2: CJC not required if using thermocouple for resistance only.

Note: Use 1794-TB2 and -TB3 terminal base units for millivolt inputs only.

These terminals not on 1794-TB2

Wiring Connections for the Thermocouple Module

Thermocouple

1794-TB2, -TB3 Terminal Base Units

1794-TB3T Terminal Base Unit

2

Thermocouple

Channel

High Signal

Terminal (+)

Low Signal

Terminal (–)

Shield

Return

High Signal

Terminal (+)

Low Signal

Terminal (–)

Shield

Return

1

0

0

1

17

0

1

39

1

2

3

19

2

3

40

2

4

5

21

4

5

41

3

6

7

23

6

7

42

4

8

9

25

8

9

43

5

10

11

27

10

11

44

6

12

13

29

12

13

45

7

14

15

31

14

15

46

24V dc Common

16 thru 33

16, 17, 19, 21, 23, 25, 27, 29, 31 and 33

+24V dc power

1794-TB2 – 34 and 51; 1794-TB3 – 34 thru 51

34, 35, 50 and 51

1

Terminals 39 to 46 are chassis ground.

2

Terminals 36, 37, 38 and 47, 48, 49 are cold

junction compensator connections.