Calibrating Your Module

Publication 1794-6.5.7 – April 1997

The

button populates the screen with the actual

values appearing at the inputs. Note that there is an implied decimal
point to the left of the last 2 digits.. For example, channel 0 data
value reads 7500. The actual reading is 75.00mV.

After both offset and gain calibrations are successful, click on

.

You will be returned to the module configuration screen. Either save
to the device (adapter), or save to a file by clicking on the
appropriate button.