Block Transfer Programming

Publication 1771ĆUM006B-EN-P - June 2002

Rung Descriptions

Rungs 1 and 2 - These rungs request the block transfer write (BTW)
and block transfer read (BTR) operations.

Rung 3 - When the processor successfully completes a BTR
operation, it sets the done (DN) bit and enables the file-to-file move
(FFM) instruction. The FFM instruction moves the BTR data file
(CCC-DDD) into a storage data file (EEE-FFF). This prevents the
processor from using invalid data if a block transfer communications
fault should occur.

Figure 6.4

Example Ladder Logic for PLCĆ2 Block Transfer

010

EN

16

110

DN

16

010
EN

17

110
DN

17

0053

EN

17

0053

DN

15

110

17

1

2

15963

BLOCK XFER WRITE
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

0050

101

0

0200 - 0277

FILE TO FILE MOVE
COUNTER ADDR:
POSITION:
FILE LENGTH:
FILE A:

0053

001
001

0203 - 0203

FILE R:
RATE PER SCAN

0204 - 0204

001

BLOCK XFER READ
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

0051

101

0

0203 - 0302

For PLC-2 family processors, we recommend that you set the block
length to zero. Then the module determines the number of transfer
words. The 1771-IJ/IK defaults to 3 words in a BTW and 1 word in
a BTR if you program a block length of zero.