2–7

Preliminary Adjustments

Publication 1771ĆUM006B-EN-P - June 2002

No special filtering is provided on channel B, since the filtering
necessary for a mechanical switch would defeat the purpose of a very
fast count direction change that is not dependent on the processor
scan time. Therefore, a transistor switch or gate should be used to
pull the channel B input low, sinking 10mA at 12V dc or 20mA at
24V dc. The count changes direction in less than 10 microseconds
from the time channel B input changes state.

Refer to the connection diagrams (Figures 3.1 and 3.2) for
interfacing different devices.

Switch assembly settings-these features are selected on two switch
assemblies that are located on the circuit board underneath the
component cover.

To select these options, proceed as follows:

1. Take off the left-side cover by removing the four slotted screws.

2. Refer to Figure 2.3. Identify the programming option switch

assembly (SW-1) and the input configuration switch assembly
(SW-2).

Figure 2.4

Location ofSwitch Assemblies

159 47

O

N

O

F

F

O N O F F

Input

Configuration

Switch

Assembly SWĆ2

Programming

Options

Switch

Assembly SWĆ1

Setting Switch Assemblies