5–10

Single Transfer Programming

Publication 1771ĆUM006B-EN-P - June 2002

Figure 5.6

Scan Counter Ć PLCĆ2 Processors

030

CTU

PR003

AC000

030

CTU

PR003

AC000

Branch End

Instruction

15957

The output instruction of both rungs in Figure 5.6 is an up-counter
(CTU) instruction. The first rung, since it is unconditional, is always
true. The second rung, since a branch end instruction by itself is
always false, sets the conditions for the counter as false. Because an
up-counter (CTU) increments for each false to true transition, CTU
030 registers one count each time the program scan occurs.

Scan Counter Ć PLC Processor

Figure 5.7 shows an example scan counter that can be used for a
PLC processor. Because the I/O and program scans of this processor
are asynchronous, this scan counter differs in form and operation
from the scan counter for PLC-2 processors.

Figure 5.7

Scan Counter Ć PLC Processor

200

CTU

PR006

AC000

3

Rung

1

2

11111

11111

L

20017

20017

/

No.

15958

/