3–4

Installation

Publication 1771ĆUM006B-EN-P - June 2002

Figure 3.2

Connection Diagram Showing Typical 1771ĆIK Counter Applications with

External Count Direction

Common

Channel B

Common

Marker

Common

Not

Assigned

12-24V

12-24V

12-24V

Module External

Power Supply

Not

Assigned

Counter

Device

Ground at

I/O Chassis Only

Transistor

Switch

Limit

Switch

Common

15949

Channel A

1
2
3
4
5
6
7
8
9

10

11
12

1
2
3
4
5
6
7
8
9

10

11
12

-

+

Output #1

12-24V dc

Isolated Power

Supply

Ifnecessary

Ifmultiple power sources are used, maintain isolation between supplies.

Output #2

Note: Use isolated external supplies as shown here, or use a single supply as shown on figure 3.1.

Note: The module must be placed in a single module group (0-1).

dc Load

dc Load

dc

The cable has a foil shield with a bare drain wire. The drain wire
should be connected to the enclosure ground at an I/O chassis
mounting bolt or stud. Connect the drain wire at only one end. The
foil and drain at the other end of the cable, which connects to the
device, should be cut short and taped back to insulate it from any
electrical contact.