Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 62
![background image](/manuals/578470/62/background.png)
4-26
General Operation
1403-IN001A-US-P
Table 4.14 Snapshot Log Parameters for the Power Block
Parameter
Description
Range
Default
Phase 1 Power
Power of phase 1 signed to show direction.
0 to 999.9x10
22
Watts
Phase 2 Power
Power of phase 2 signed to show direction.
0 to 999.9x10
22
Watts
Phase 3 Power
Power of phase 3 signed to show direction.
0 to 999.9x10
22
Watts
3-Phase Total Power
Total power of phase 1, 2, and 3 signed to show direction.
0 to 999.9x10
22
Watts
Phase 1 Reactive Power
Reactive power of phase 1 signed to show direction.
0 to 999.9x10
22
Vars
Phase 2 Reactive Power
Reactive power of phase 2 signed to show direction.
0 to 999.9x10
22
Vars
Phase 3 Reactive Power
Reactive power of phase 3 signed to show direction.
0 to 999.9x10
22
Vars
3-Phase Total Reactive Power
Total reactive power of phases 1 to 3 signed to show direction. 0 to 999.9x10
22
Vars
Phase 1 Apparent Power
Apparent power of phase 1.
0 to 999.9x10
22
VA
Phase 2 Apparent Power
Apparent power of phase 2.
0 to 999.9x10
22
VA
Phase 3 Apparent Power
Apparent power of phase 3.
0 to 999.9x10
22
VA
3-Phase Total Apparent Power
Total apparent power of phase 1, 2, and 3.
0 to 999.9x10
22
VA
Phase 1 True Power Factor
The ratio between the power and apparent power for phase 1;
this value is signed to show lead (+) or lag (-).
-100 to 100
Percent
Phase 2 True Power Factor
The ratio between the power and apparent power for phase 2;
this value is signed to show lead (+) or lag (-).
-100 to 100
Percent
Phase 3 True Power Factor
The ratio between the power and apparent power for phase 3;
this value is signed to show lead (+) or lag (-).
-100 to 100
Percent
Total True Power Factor
The ratio between the power and apparent power for phase 1,
2, and 3; this value is signed to show lead (+) or lag (-).
-100 to 100
Percent
Phase 1 Distortion Power Factor
The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 1.
(1)
0 to 100
Percent
Phase 2 Distortion Power Factor
The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 2.
1
0 to 100
Percent
Phase 3 Distortion Power Factor
The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 3.
1
0 to 100
Percent
Total Distortion Power Factor
The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 1, 2, and 3.
1
0 to 100
Percent
Phase 1 Displacement Power
Factor
The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 1; this value is
signed to show lead (+) or lag (-).
1
-100 to 100
Percent
Phase 2 Displacement Power
Factor
The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 2; this value is
signed to show lead (+) or lag (-).
1
-100 to 100
Percent
Phase 3 Displacement Power
Factor
The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 3; this value is
signed to show lead (+) or lag (-).
1
-100 to 100
Percent
Total Displacement Power Factor
The cosine of the difference between the phase angle of the
fundamental voltage and current for phase 1, 2, and 3; this
value is signed to show lead (+) or lag (-).
1
-100 to 100
Percent
(1) This value has the same update rate as the harmonic analysis.