Data logging – Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 59
General Operation
4-23
1403-IN001A-US-P
Data Logging
The Powermonitor II provides three data logs:
•
Event log
•
Snapshot log
•
Min/Max log
Each record of the three logs is date and time-
stamped to the nearest one hundredth of a second. All
of the records are stored in battery powered non-
volatile RAM. The data logs remain in memory as
long as power is applied to the Master Module or the
battery has a usable charge. In the event that power is
removed from the Master Module and the battery is
removed or discharged, all of the data logs will be
automatically cleared.
Event Log
The Event log consists of the 100 most recent events
that occurred in the Powermonitor II. This log is a
circular buffer. When the buffer is full, the newest
event overwrites the oldest event. A list of the events
is shown in Table 4.11.
Table 4.11 Event Codes
Event Type
Event Type
Displayed by
Display
Module
Event Type
for Smart
Comm.
Card
Event Command
Code for Smart
Comm. Card
No Event
No Evnt
0
0
Setpoint
Activated
Set##A
1
Setpoint Number
(1-20)
Setpoint
Deactivated
Set##D
2
Setpoint Number
(1-20)
Relay Forced
Energized
Rly# F1
3
Relay Number (1-
2)
Relay Forced
De-energized
Rly# F0
4
Relay Number (1-
2)
Relay Forced
Released
Rly# NF
5
Relay Number (1-
2)
Status Input
Set
S# On
6
Status Input
Number (1-4)
Status Input
Cleared
S# Off
7
Status Input
Number (1-4)
kWh Counter
Set
Wh Set
8
1
Kvarh
Counter Set
VarhSet
8
2
Snapshot
Log Cleared
SnapClr
8
3
Min/Max Log
Cleared
↓
/
↑
Car
8
4
Factory
Defaults
Restored
FactCfg
8
5
Status Input
Counter 1
Cleared
S1 Clr
8
6
Status Input
Counter 2
Cleared
S2 Clr
8
7
Status Input
Counter 3
Cleared
S3 Clr
8
8
Status Input
Counter 4
Cleared
S4 Clr
8
9
Battery
Usage
Counter
Cleared
BattClr
8
10
Power Up
Pwr On
9
0
Power Down Pwr Off
10
0
Self-test
Error
ST ####
(1)
11
Hexadecimal Self-
test Code (Refer
to Table 4.L)
Time Set
TimeSet
12
0
Device
Reconfigured
New Cfg
13
0
Setpoint
Reconfigured
Set Cfg
14
0
(1) # indicates a numeric digit.
Table 4.11 Event Codes
Event Type
Event Type
Displayed by
Display
Module
Event Type
for Smart
Comm.
Card
Event Command
Code for Smart
Comm. Card