Commands – Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 46

4-10
General Operation
1403-IN001A-US-P
Commands
Table 4.3 displays the commands for the
Powermonitor II. The gray scale indicates which
commands are available through the Display Module,
the Smart Communication Card, or both.
Display Module and Smart Communication Card
Display Module Only
Smart Communication Card Only
Table 4.3 Commands
Parameter
Description
Range
Force Relay #1 and #2
Forces Relay #1 and #2 to a known state in which the relay
remains at that state until the force is removed.
1 = Energize
2 = De-energize
4 = No Force (Automatic)
Clear Min/Max Log
Resets the Min/Max log with the current real time metering
information.
No
Yes
Clear Snapshot Log
Clears all entries in the Snapshot log buffer.
No
Yes
Clear kWH Counter
Resets the kWH counter to zero.
No
Yes
Clear kVarH Counter
Resets the kVarH counter to zero.
No
Yes
Set kWH Counter
Sets the kWH counter to the user specified value. (0 to clear)
-999.9x10
9
to 999.9x10
9
Set kVarH Counter
Sets the kVarH counter to the user specified value. (0 to clear)
-999.9x10
9
to 999.9x10
9
Clear Status Input #1 to #4
Counter
Resets Status Input #1 to #4 Counter to zero.
No
Yes
Clear Battery Usage
Counter
Resets the Battery Usage Counter to zero.
No
Yes
Restore Factory Defaults
Restores all of the Powermonitor II configuration parameters with
the factory default values.
No
Yes
Clear Hold of Oscillograph
Data
(1)
Allows the user to enable oscillography when the oscillography
type is set to Hold.
No
Yes
Trigger an Oscillograph
1
Allows the user to manually trigger a simultaneous 7 Channel 2-
Cycle and 2 Channel 12-Cycle oscillograph.
No
Yes
Set Harmonic Analysis
Channel Request
1
Specifies the particular input channel for harmonic analysis
information to be returned through the Smart Communication
Card.
1 = Phase 1 Voltage
2 = Phase 1 Current
3 = Phase 2 Voltage
4 = Phase 2 Current
5 = Phase 3 Voltage
6 = Phase 3 Current
7 = Phase 4 Current
Set Oscillography Channel
Request
1
Specifies the particular input channel for an oscillogram to be
returned through the Smart Communication Card.
1 = 2 Cycle Phase 1 Voltage
2 = 2 Cycle Phase 1 Current
3 = 2 Cycle Phase 2 Voltage
4 = 2 Cycle Phase 2 Current
5 = 2 Cycle Phase 3 Voltage
6 = 2 Cycle Phase 3 Current
7 = 2 Cycle Phase 4 Current
8 = 12 Cycle Channel A
9 = 12 Cycle Channel B
Select Setpoint Number
Specifies the particular setpoint information to be returned through
the Smart Communication Card.
1 to 20
(1) Available on 1403-MM only.