Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 57

General Operation
4-21
1403-IN001A-US-P
Table 4.9 Setpoint Type
Setpoint
Type
Description
0
Not used (inactive)
1
Voltage (any 1 of three phases, L-N in Single
Phase/Wye Modes, L-L in Delta/Open-Delta
Modes)
2
Current (any 1 of three phases)
3
Voltage unbalance
4
Current unbalance
5
Vaux voltage
6
Neutral (I4) current
7
Total kW
8
Total kVAR
9
Total kVA
10
Total true power factor
11
Total displacement power factor
12
Total distortion power factor
13
KW demand
14
KVAR demand
15
KVA demand
16
Current demand
17
Type 1 predictive demand A
18
Type 1 predictive demand W
19
Type 1 predictive demand VAR
20
Type 1 predictive demand VA
21
Type 2 predictive demand A
22
Type 2 predictive demand W
23
Type 2 predictive demand VAR
24
Type 2 predictive demand VA
25
Type 3 predictive demand A
26
Type 3 predictive demand W
27
Type 3 predictive demand VAR
28
Type 3 predictive demand VA
29
Frequency
30
Phase rotation
31
(1)
K-factor: voltage (any 1 of three phases)
32
(1)
K-factor: current (any 1 of three phases)
33
(1)
K-factor: neutral current
34
(1)
Crest factor: voltage (any 1 of three phases)
35
(1)
Crest factor: current (any 1 of three phases)
36
(1)
Crest factor: neutral current
37
(1)
TIF: voltage (any 1 of three phases)
38
(1)
TIF: current (any 1 of three phases)
39
(1)
TIF: neutral current
40
IEEE THD: voltage (any 1 of three phases)
41
IEEE THD: current (any 1 of three phases)
42
IEEE THD: neutral current
43
IEC THD: voltage (any 1 of three phases)
44
IEC THD: current (any 1 of three phases)
45
IEC THD: neutral current
46
(1)
IEEE519: voltage (any 1 of three phases)
47
(1)
IEEE519: current (any 1 of three phases)
48
(1)
IEEE519: neutral current
49
Status input #1
50
Status input #2
51
Status input #3
52
Status input #4
53
Any status input
54
Battery usage timer
(1) Available on 1403-MM only.
Table 4.10 Setpoint Action Type
Setpoint Action
Type
Description
0
No action
1
Energize relay1 and set alarm flag1
2
Energize relay2 and set alarm flag2
3
Set alarm flag3
4
Set alarm flag4
5
Set alarm flag5
6
Set alarm flag6
7
Set alarm flag7
8
Set alarm flag8
9
Set alarm flag9
10
Set alarm flag10
11
Set alarm flag11
12
Set alarm flag12
13
Set alarm flag13
14
Set alarm flag14
15
Set alarm flag15
16
Set alarm flag16
17
1
Initiate oscillograph
18
Perform snapshot
19
Clear kWh power counter
20
Clear kVARh power counter
Table 4.9 Setpoint Type
Setpoint
Type
Description