Log selection command table write (file n22), B-23 – Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual
Page 37

Publication 1403-IN005A-EN-P
Ethernet Communication Card Data Tables B-23
Table B.21 Log Selection Command Table Write (File N22)
Param. No.
Parameter Name
Master Module Range
Element
Range
12.1
Selected Log
23 = Event Log
24 = Min/Max Log
54 = Snapshot V/I Log, or
16, 8, 3 and 7, 1
parameter records
59 = Snapshot Power Log
1
23, 24, 54, 59
12.2
Maximum Number of Data Sets
1 to 100 for Event Log
1 to 84 for Min/Max Log
1 to 50 for Snapshot V/I
Log
1 to 50 for Snapshot
Power Log
1 to 265 for snapshot 16
parameter log
(1)
1 to 489 for snapshot 8
parameter log
1 to 846 for snapshot 4
parameter log
1 to 100 for snapshot 7
parameter log
1 to 845 for snapshot 3
parameter log
1 to 1861 for snapshot 1
parameter log
2
1 to 100 for Event Log
1 to 84 for Min/Max Log
1 to 50 for Snapshot V/I
Log
1 to 50 for Snapshot
Power Log
1 to 265 for snapshot 16
parameter log
1 to 489 for snapshot 8
parameter log
1 to 846 for snapshot 4
parameter log
1 to 100 for snapshot 7
parameter log
1 to 845 for snapshot 3
parameter log
1 to 1861 for snapshot 1
parameter log
12.3
Chronology of Returned Data
0 = Reverse
1 = Forward
Note: Not used for Min/
Max Log
3
0 to 1
12.4
First Min/Max Parameter to be Returned
1 to 84
4
1 to 84
12.5
Snapshot Starting Record Offset
0 to
(parameter 12.2 max - 1)
5
0 to
(parameter 12.2 max - 1)
Reserved Word
6
Reserved Word
7
Reserved Word
8
Reserved Word
9
(1) Available on firmware V3.00 or later.