6 Product Description
Indicators
Four LED indicators provide information about the operating status of the
card.
Configuration Items
Communication
Table 3 LED Indicators
Label
Name
LED Color
LED State and Communications Condition
RDY
Ready
Red
ON = Control power applied
ON/OFF Flashing = Self-test initialization
LK
Link
Green
ON = UTP (10BaseT) cable properly connected
RX
Receive
Green
ON/OFF Flashing = Receiving Data
TX
Transmit
Green
ON/OFF Flashing = Transmitting Data
Table 4 Communication Configuration Items
Communication Parameter
Description
Range
Default
IP Address Byte a
IP address of this Powermonitor. (Normally in the form
128.1.1.1)
0 to 255
128
IP Address Byte b
1
IP Address Byte c
1
IP Address Byte d
Device ID#
Subnet Mask Byte a
Specifies the subnet mask to apply to the IP address.
Network ID and Host are specified by address class. Zero
bits in the mask indicate bit positions of the host number;
one bits are for subnet ID. (Normally in the form
255.255.255.0)
0 to 255
255
Subnet Mask Byte b
255
Subnet Mask Byte c
255
Subnet Mask Byte d
0
Physical Ethernet Port
Selects the Ethernet media (0=UTP/10BaseT, 1=AUI/
10Base5)
0 = UTP, 1 =AUI
0 = UTP
Keep Alive Time
The maximum allowable time any socket is dedicated to a
connection that is not responding.
5 to 3600 seconds
30
Inactivity Time
The maximum allowable time the entire Ethernet
communication card waits with no network activity
before rebooting.
Set parameter to zero to disable inactivity time.
0 to 1440 minutes
0 = Disabled
30
NOTE
BOOTP, the dynamic acquisition of an IP address, is
enabled when all four address bytes of the programmed IP
address are set to zero. (0.0.0.0)