See table b.6, See table b.7 – Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual
Page 22
Publication 1403-IN005A-EN-P
B-8 Ethernet Communication Card Data Tables
3.12
Present Unit Password
0 to 9999
18
0 to 9999
Reserved
19
Reserved 20
Reserved 21
Reserved
22
(1) See Table B.6 o n pageB-8 for specific command bits to enable these features.
(2) Available on firmware V3.00 or later.
Table B.5 Command Data Table Write (File N13)
Parameter No.
Parameter Name
Master Module Range
Element
Range
Table B.6 Bit Fields for Command Data Table -(Command Word 1)
Command
Bit Location and
Value
Clear Snapshot Log
b0 = 1
Clear Min_Max Log
b1 = 1
Restore Factory Default Configuration
b2 = 1
Clear Hold of Oscillograph Capture #1 (Reserved on 1403-LM)
b3 = 1
Initiate Oscillograph Capture #1 (Reserved on 1403-LM)
b4 = 1
Force Self Test
b5 = 1
Clear Status Input Counter 1
b6 = 1
Clear Status Input Counter 2
b7 = 1
Clear Status Input Counter 3
b8 = 1
Clear Status Input Counter 4
b9 = 1
Clear Battery Usage Timer
b10 = 1
Reserved
b11 = 1
Synchronize Demand Interval
b12 = 1
Clear Hold of Oscillograph Capture #2 (Reserved on 1403-LM)
b13 = 1
Initiate Oscillograph Capture #2 (Reserved on 1403-LM)
b14 = 1
Table B.7 Bit Fields for Command Data Table - (Command Word 2)
Command
Bit Location and
Value
Set Analysis Channel Request (DV1)
b0 = 1
Set Oscillogram Channel Request (DV2)
(Not Available on 1403-LM)
b1 = 1
Set W Hours (DV3)
b2 = 1
Set VAR Hours (DV4)
b3 = 1