Table b.9 real-time power data - read (file f15), Real-time power data - read (file f15), B-10 – Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual
Page 24
![background image](/manuals/578454/24/background.png)
Publication 1403-IN005A-EN-P
B-10 Ethernet Communication Card Data Tables
4.22
Reserved Word
25
4.23
Last Cycle Frequency
20.0 to 132.0
26
0 to 9999
4.24
Phase Rotation
0 = No Rotation
1 = ABC
2 = ACB
27
0 to 2
Reserved Word
28
Reserved Word
29
Table B.8 Voltage/Current Data - Read (File F14)
Parameter No.
Parameter Name
Master Module Range
Element
Range
Table B.9 Real-Time Power Data - Read (File F15)
Parameter No.
Parameter Name
Master Module Range
Element
Range
5.1
Time Stamp
Year
1
32-bit Float
Month, Date
2
32-bit Float
Hour, Minute
3
32-bit Float
Seconds, Hundredths
4
32-bit Float
5.2
L1 Real Power
0 to 9999x10
21
W
5
0 to 9999x10
21
5.3
L2 Real Power
0 to 9999x10
21
W
6
0 to 9999x10
21
5.4
L3 Real Power
0 to 9999x10
21
W
7
0 to 9999x10
21
5.5
Total Real Power
0 to 9999x10
21
W
8
0 to 9999x10
21
5.6
L1 Reactive Power
0 to 9999x10
21
VAR
9
0 to 9999x10
21
5.7
L2 Reactive Power
0 to 9999x10
21
VAR
10
0 to 9999x10
21
5.8
L3 Reactive Power
0 to 9999x10
21
VAR
11
0 to 9999x10
21
5.9
Total Reactive Power
0 to 9999x10
21
VAR
12
0 to 9999x10
21
5.10
L1 Apparent Power
0 to 9999x10
21
VA
13
0 to 9999x10
21
5.11
L2 Apparent Power
0 to 9999x10
21
VA
14
0 to 9999x10
21
5.12
L3 Apparent Power
0 to 9999x10
21
VA
15
0 to 9999x10
21
5.13
Total Apparent Power
0 to 9999x10
21
VA
16
0 to 9999x10
21
5.14
L1 True PF
-100.0 to +100.0
17
-100.0 to +100.0
5.15
L2 True PF
-100.0 to +100.0
18
-100.0 to +100.0
5.16
L3 True PF
-100.0 to +100.0
19
-100.0 to +100.0
5.17
Total True PF
-100.0 to +100.0
20
-100.0 to +100.0
5.18
L1 Displacement PF
(1)
-100.0 to +100.0
21
-100.0 to +100.0
5.19
L2 Displacement PF
-100.0 to +100.0
22
-100.0 to +100.0
5.20
L3 Displacement PF
-100.0 to +100.0
23
-100.0 to +100.0
5.21
Total Displacement PF
-100.0 to +100.0
24
-100.0 to +100.0