Phase failure (based on voltage measurement), Table 3.aa, Phase sequence setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 87: Table 3.ab, Phase failure setting parameters

Functions 3-54
Publication 825-UM001B-EN-P January 2001
Table 3.AA Phase Sequence Setting Parameters
➊ If auxiliary relays #2 and #3 are assigned to the communication (refer to page
) they cannot be selected
here.
Phase Failure (Based on Voltage Measurement)
Function
A phase failure is recognized by measuring the voltages before the switchgear and thus with
the motor at standstill. (With phase failure protection where the phase currents are measured,
the motor first has to be switched on, although it cannot start with only two phases.)
Table 3.AB Phase Failure Setting Parameters
➊ If auxiliary relays #2 and #3 are assigned to the communication (refer to page
) they cannot be selected
here.
Function
Factory setting
Off
Tripping Delay
Factory setting
1 s
Output Relay ➊
Selection (relays)
MR, AL, #1…#5
Factory setting
MR
ATTENTION
!
The phase sequence of the motor supply can be monitored only at the
point of measurement (usually before the contactor). Exchanged leads
between this point and the motor cannot be recognized.
Function
Factory setting
Off
Tripping Delay
Factory setting
2 s
Output Relay ➊
Selection (relays)
MR, AL, #1…#5
Factory setting
MR