Reset
When the motor is at standstill, a trip condition can be reset.
Kinds of Reset
•
Manual reset — Press the reset button on the Bulletin 825 for at least 200 ms
•
Remote reset — Short circuit terminals Y2l/Y22
•
Automatic reset — In the mode “set values”, set automatic reset for:
•
Thermal trip
•
PTC trip
•
PT100 trip
Reset Conditions
•
Thermal — As soon as the temperature rise has dropped to the preset reset
threshold.
•
PTC detector — As soon as the temperature is below the reset threshold
•
PT100 detector — As soon as the temperature is below the tripping threshold.
•
Asymmetry/Phase failure — Manual or remote reset possible
•
All other trips — Can be reset immediately.
Table 3.V Reset Setting Parameters
Function of the Cat. No. 825-MST Option Card
Short-Circuit
Heavy phase currents caused by short circuits between phases and from phase to earth are
detected by the Cat. No. 825-MST option card. The supply can be interrupted immediately by
controlling the power switching device (e.g., circuit-breaker).
Short-circuit protection is always active. Therefore, the response level must be set somewhat
higher than the maximum starting current.
Setting range
Manual/Automatic
Factory setting
Manual
Reset Threshold of the Thermal Trip
Setting range
10…100%
Factory setting
70%
Setting increments
5%