Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 116
5-13 Setting the Operational Parameters
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M… Operating Parameters (Continued)
➊ If Phase-Rever Trip is set to “off”, the programming menu skips to parameter Phase Loss Trip.
➋ If Phase Loss Trip is set to “off”, the programming menu skips to parameter PT100 Prot.
➌ If PT100 Prot is set to “off”, the programming menu skips to parameter Output 4…20 mA.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Control input #2,
continued
825-MST
Not disabled/
disabled
Underload protection
Active/locked out
Not disabled/
disabled
Limiting starts/hour
Active/locked out
Not disabled/
disabled
PTC protection
Active/locked out
Not disabled/
disabled
PT100 (RTD) protection
Active/locked out
Phase sequence
protection
825-MLV
On/Off ➊
Phase sequence protection
(based on motor supply
voltage)
On/Off
All relays
Phase sequence protection
Assignment of output relay
Phase failure
825-MLV
On/Off ➋
Phase failure
(based on motor supply
voltage) On/Off
All relays
Phase failure
Assignment of output relay
PT 100 (RTD)
temperature sensor
825-MMV
On/Off ➌
PT100 protection
(stator/bearings)
On/Off
On/Off
PT100 #1 protection
On/Off
50…200
PT100 #1
Tripping temperature
On/Off
PT100 #2 protection
On/Off
50…200
PT100 #2
Tripping temperature
UNDERLOAD PROT
NOT DISABLED
START INHIBIT
NOT DISABLED
PTC PROT
NOT DISABLED
PT100 PROT
NOT DISABLED
PHASE-REVER TRIP
OFF
PHASE-REVER TRIP
MAIN RELAY
PHASE LOSS TRIP
OFF
PHASE LOSS TRIP
MAIN RELAY
PT100 PROT
OFF
PT100 #1 TRIP
OFF
#1 TRIP TEMP
50 °C
PT100 #2 TRIP
OFF
#2 TRIP TEMP
50 °C