5-15 Setting the Operational Parameters
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M… Operating Parameters (Continued)
➊ If Tamb in Thermal Image is set to “off”, the programming menu skips to parameter Output 4…20 mA.
➋ Limiting winding temperatures of the three insulations classes: E = 120°C, B = 130°C, F = 155°C. When the
ambient temperature is taken into consideration, the insulation class needs to be programmed for correction
of the thermal model. Without using PT100 #7 as the ambient temperature input, the thermal model bases
the thermal calculation on an ambient temperature of 40°C.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
PT 100 (RTD)
temperature sensor,
continued
825-MMV
On/Off
PT100 #3 warning
On/Off
50…200
PT100 #3
Warning temperature
On/Off
PT100 #4 warning
On/Off
50…200
PT100 #4
Warning temperature
On/Off
PT100 #5 warning
On/Off
50…200
PT100 #5
Warning temperature
On/Off
PT100 #6 warning
On/Off
50…200
PT100 #6
Warning temperature
AL,
#1…#3
PT100, #1…#6 warning
Assignment of output relay
On/Off ➊
PT100 #7, allowance for
ambient temperature in
thermal simulation
B, E, F
Insulation class of
winding ➋
Analog output
825-MST
Thermal utiliz
, Motor
PT100 max.
Using the analog output for:
thermal utilization,
motor current,
max. PT100 temperature
PT100 #3 WARNING
OFF
#3 WARNING TEMP
50 °C
PT100 #4 WARNING
OFF
#4 WARNING TEMP
50 °C
PT100 #5 WARNING
OFF
#5 WARNING TEMP
50 °C
PT100 #6 WARNING
OFF
#6 WARNING TEMP
50 °C
#1-6 WARNING
OFF
Tamb IN TH IMAGE
OFF
INSULATION CLASS
B
OUTPUT 4…20 mA
THERMAL