Chapter 5 - Parameters and Programming

5–10

Program Group – Preset Speed Model Only

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

61

[Preset Frequency 0]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

3 Hz

62

[Preset Frequency 1]

The programmed value sets the frequency that

the controller outputs when selected

0 to 240

0.1 Hz

20 Hz

63

[Preset Frequency 2]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

30 Hz

64

[Preset Frequency 3]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

40 Hz

65

[Preset Frequency 4]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

45Hz

66

[Preset Frequency 5]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

50 Hz

67

[Preset Frequency 6]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

55 Hz

68

[Preset Frequency 7]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

60 Hz

69

[Accel Time 2]

The programmed value sets the acceleration time for P65

to P68 [Preset Frequencies 4-7]. The rate is linear for any increase in command
frequency unless P53 - [S-Curve] is set to a value other than 0"

0.1 to 600

0.1 Sec.

20.0 Sec.

70

[Decel Time 2]

The programmed value sets the deceleration time for P65

to P68 [Preset Frequencies 4-7]. The rate is linear for any decrease in command
frequency unless P53 - [S-Curve] is set to a value other than 0"

0.1 to 600

0.1 Sec.

20.0 Sec.

=

This parameter applies only to the Preset Speed model

Preset Accel/Decel Chart For Preset Speed Model Only

TB3–

SW3

TB3–

SW2

TB3–

SW1

Preset

Accel

Decel

0

0

0

Preset 0

0

0

1

Preset 1

P30 -[Accel Time 1]

P31 - [Decel Time 1]

0

1

0

Preset 2

P30 -[Accel Time 1]

P31 - [Decel Time 1]

0

1

1

Preset 3

1

0

0

Preset 4

1

0

1

Preset 5

P69 - [Accel Time 2]

P70 - [Decel Time 2]

1

1

0

Preset 6

P69 - [Accel Time 2]

P70 - [Decel Time 2]

1

1

1

Preset 7

Refer to Figure 2.5 for the Preset Speed model control wiring diagram.