Control wiring (continued) – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual
Page 21
![background image](/manuals/578089/21/background.png)
Chapter 2 - Installation/Wiring
2–7
Use P46 – [Input Mode] to select the control
method for start, stop, and direction control.
There are four settings from which to choose:
D Setting 0 – three wire control (this is the
factory default setting).
D Setting 1 – two wire “run forward/run
reverse”control. Note: The “run” inputs must
be maintained.
D Setting 2 – program keypad module control.
See page 3–1.
D Setting 3 – momentary “run forward/run
reverse” control. Note: The “run” inputs do
not need to be maintained.
8
7
6
5
4
3
2
1
9
10
Reverse
Start
Common
Stop
Signal
Specification
Contact closure input required
to operate controller
À
Common
Â
Contact closure input
À
Contact closure input
À
Terminal
TB3
11
8
7
6
5
4
3
2
1
9
10
Run Reverse
Run Forward
Common
Stop
Signal
Specification
Contact closure input
required to operate controller
À
Common
Â
Contact closure input
À
Contact closure input
À
Terminal
TB3
11
Á
8
7
6
5
4
3
2
1
9
10
Run Reverse
Run Forward
Common
Stop
Signal
Specification
Contact closure input
required to operate controller
À
Common
Â
Contact closure input
À
Contact closure input
À
Terminal
TB3
11
À
Internal 12V supply.
Á
If both Run Forward and Run Reverse inputs are closed
at the same time an undetermined state could occur.
Figure 2.6 - TB3 Three Wire control (Setting 0)
Figure 2.7 - TB3 Two wire Run forward/run reverse
control (Setting 1)
Figure 2.8 - TB3 Momentary Run forward/run
reverse" control (Setting 3)
Control Wiring (continued)
Â
Do not exceed control wiring length of 15 meters (50
feet). Control signal cable length is highly dependent
on electrical environment and installation practices.
To improve noise immunity the control terminal block
common must be connected to earth ground.
Consult factory for longer control signal cable length
applications.
Explanation of Symbols:
Á
= N.C. Momentary Contact
= N.O. Momentary Contact
= N.O. Maintained Contact
= N.C. Maintained Contact
ATTENTION: The program keypad
module stop key simulates momentary
pushbutton operation. For “two wire”
control schemes (P46 – [Input Mode],
setting “1”) the program keypad module
stop button will only provide a “stop”
function while the stop key is depressed.
ATTENTION: When changing the
parameter setting for P46 – [Input
Mode], you must cycle power for the
change to take effect.
Shielded Wire
Shielded Wire
Shielded Wire