Chapter 5 - Parameters and Programming
5–9
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
54
[Clear Fault]
Setting this parameter to a 1" performs a fault reset. When
the fault reset function is complete, the value is automatically set back to 0".
Note: This parameter cannot be programmed while the controller is running.
0 to 1
Numeric
Value
0
55
[Memory Probe Address]
Used by Allen-Bradley field service
personnel.
Numeric Value
Numeric
Value
Numeric
Value
56
[Reset Defaults]
All parameters and their associated factory defaults are
reset when set to a value of 1". When the default function is complete, this
parameter will set itself back to a 0". This parameter cannot be programmed
while the controller is running. Note: An F48 - [Reprogram Fault] will occur
and must be cleared by cycling the STOP input to the controller.
Note: P46-[Input Mode Select] factory defaults to 3 wire" control. If using
keypad control, change parameter setting back to a 2" to regain program keypad
control.
0 to 1
Numeric
Value
0
57
[Program Lock]
When set to a 1", this parameter protects all controller
parameters from being changed by unauthorized personnel.
0 to 1
Numeric
Value
0
Program Group – Analog Signal Follower Model Only
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
ЙЙЙ
ЙЙЙ
ЙЙЙ
58
[Internal Frequency]
Digital frequency setpoint from the program
keypad module. Value of frequency command when P59 - [Frequency Select] is
set to a 1".
0 to 240
0.1 Hz
60.0
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
59
[Frequency Select]
Selects the source of the frequency command for
the controller.
Settings:
0 = frequency source from analog input to TB3 control terminal
block.
1 = frequency source from digital setpoint programmed into
P58 - [Internal Frequency].
0 to 1
Numeric
Value
0=Analog
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
ЙЙЙ
60
[Analog Scale Teach]
Scales the 0-10V
À
,4-20 mA analog input, or
remote potentiometer input to operate between P32 - [Minimum Frequency] and
P33 - [Maximum Frequency]. To scale to P33 - [Maximum Frequency], set
analog input to maximum value, increment parameter to a 1", and then press the
enter key. To scale to P32 - [Minimum Frequency], set analog input to minimum
value, increment parameter to a 2", and then press the enter key. Note: The
parameter resets to 0" after you press the enter key.
À
If you are using a bipolar input (-10 to +10V), do not scale the input to the
minimum frequency setting.
0 to 2
Numeric
Value
0
ЙЙЙ
ЙЙЙ
=
This parameter applies only to the Analog Signal Follower model.