Program group, 41 [motor overload select, 42 [motor overload current – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual
Page 32: 43 [current limit, 44 [dc hold time, 45 [dc hold voltage, Dc brake mode, Ramp mode, P# parameter description
Chapter 5 - Parameters and Programming
5–6
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
41
[Motor Overload Select]
Selects the derating factor for the I
2
t
overload function.
Min Derating
Max Derating
% Base Speed
% Base Speed
0 25 50 75100 125 150 175 200
0 25 50 75 100125 150 175 200
[Overload Current]
%
of
Setting
[Overload Current]
%
of
Setting
100
80
60
40
20
100
80
60
40
20
Settings:
0 = No Derating
1 = Minimum Derating
2 = Maximum Derating
100
80
60
40
20
0 25 50 75 100 125150 175 200
% Base Speed
No Derating
[Overload Current]
%
of
Setting
0 to 2
Numeric
Value
0
42
[Motor Overload Current]
Set to motor nameplate full load Amps
(FLA).
25% to 200%
.01 Amperes
115% of
Controller
Rating
43
[Current Limit]
Maximum output current allowed before current limiting
occurs. Value set in percent of controller rated output current.
20% to 190%
1 %
150%
44
[DC Hold Time]
Time that P45 - [DC Hold Volts] voltage will be applied
to the motor when P34 - [Stop Mode Select] is set to either DC Brake" or
Ramp" mode.
0 to 15
1 Second
0 Seconds
45
[DC Hold Voltage]
DC Voltage level applied to the motor during braking
when P34 - [Stop Mode Select] is set to either DC Brake" or Ramp" mode.
0 to 115
1 Volt
0 Volts
[DC Hold Time]
y
Stop Command
[DC Hold Voltage]
Time
Speed
Voltage
Volts and Speed
DC Brake Mode
Volts and Speed
y
Voltage
Stop Command
[DC Hold Time]
[DC Hold Voltage]
Time
Speed
Ramp Mode