Chapter 5 - Parameters and Programming
5–2
Display Group Parameters
This group of parameters consists of commonly viewed controller operating conditions such as controller
output frequency, output voltage, output current and frequency command. All parameters in this group
are read only.
Display Group
1. While in display mode, increment to the parameter you wish to see when the controller powers up.
You may find it necessary for the controller to display a specific parameter each time it is powered up. (This is
especially useful when troubleshooting and making system adjustments). Follow these steps to make the controller
power up at a specific display parameter:
2. Press the key twice. When you cycle power to the controller it will display the parameter that you set.
Note: If you change any program group parameters, the controller (when powered up) will show the last display
parameter that was present before you went into program mode.
P#
Parameter Description
Min/Max
Range
Units
01
[Output Frequency]
Displays the output frequency at TB2 terminals
T1, T2 and T3 (U, V and W).
0 to 240 Hz
0.1 Hz
02
[Output Voltage]
Displays the output voltage present at TB2 terminals
T1, T2 and T3 (U, V and W).
0 to [Max Voltage]
1 Volt
03
[Output Current]
Displays the output current present at TB2 terminals
T1, T2 and T3 (U, V and W).
0 to 2 Times
Controller Rated
Output Current
0.01Amps
04
[Output Power]
Displays the output power present at TB2 terminals T1,
T2 and T3 (U, V and W).
0 to 2 Times Rated
Controller Output
Power
0.01 kW
05
[Bus Voltage]
Displays the DC Bus Voltage level.
0 to 400 - [230V]
0 to 800 - [460V]
1 Volt
06
[Frequency Command]
Displays the frequency that the controller
is commanded to output. This command may come from any of the frequency
sources selected by
P59 - [Frequency Select]
or from a currently selected preset
frequency.
0 to 240
0.1 Hz
07
[Last Fault]
Displays the coded last fault number. If a fault is currently
active (has not been cleared) the display will flash. See Chapter 6 for fault code
descriptions.
0 to 48
Numeric Value
08
[Heatsink Temperature]
Displays the temperature of the controller
heatsink.
0 to 150
1 Degree C
09
[Controller Status]
Displays the status of the controller in a binary
coded format.
Bit 3
Bit 2
Bit 1
Bit 0
Running
Accel
Forward
Decel
Note: A 0" = inactive
and a 1" = active.
0000 to 1011
Binary Number