Original instructions, 3 timing behavior of the ossds – Rockwell Automation 442L SafeZone Singlezone & Multizone Safety Laser Scanner User Manual
Page 45

R
SafeZone™ Safety Laser Scanner User Manual
10000073050, July 2011 43
Original instructions
Basic response time for various resolutions
The following basic response times apply for the internal OSSDs with
standard multiple sampling of 2 without taking into account the
switching time for the monitoring cases.
Table 23: Response time with a resolution of 30 mm (hand
detection)
Table 24: Response time with a resolution of 40 mm (hand
detection)
Table 25: Response time with a resolution of 50 mm (leg
detection, stationary)
Table 26: Response time with a resolution of 70 mm (leg
detection, mobile)
Table 27: Response time with a resolution of 150 mm (body
detection)
Multiple sampling
The SafeZone safety laser scanner is always set to a minimum of two times
multiple sampling. From a multiple sampling of three you must add a
supplement to the response time. The related supplement is dependent on
the basic response time and the multiple sampling.
Table 28: Supplements for multiple sampling
11.3 Timing behavior of the OSSDs
The SafeZone safety laser scanner tests the OSSDs immediately after
switching on and then at regular intervals. For this purpose the SafeZone
safety laser scanner briefly switches off both OSSDs (for 300 μs) and
checks whether the channels are electrically isolated during this period.
Figure 64: Diagram of the test pulse at the OSSDs
Approx. 15 ms after the switch on of the OSSDs, the SafeZone safety
laser scanner performs the first voltage test
and then after a half basic
response time (see “Basic response time for various resolutions” on page
43) performs a second voltage test
.
After a further half basic response time of the SafeZone safety laser
scanner there is a shut-down test
, 120 ms later a further voltage test .
Then the SafeZone safety laser scanner performs a shut-down test and a
voltage test alternately at an interval of 120 ms. Figure 66, Figure 67 and
Figure 68 show the pulse durations for the individual tests.
B
=
tB= Basic response time
T
MFA
=
Supplement due to multiple sampling > 2
d
=
Resolutions of the SafeZone safety laser scanner (mm)
Maximum Possible Protective Safety Field
Size
Basic Response Time
1.90 m
60 ms
2.80 m
120 ms
Maximum Possible Protective Safety Field
Size
Basic Response Time
2.60 m
60 ms
3.80 m
120 ms
Maximum Possible Protective Safety Field
Size
Basic Response Time
3.30 m
60 ms
4.80 m
120 ms
Maximum Possible Protective Safety Field
Size
Basic Response Time
4.70 m
60 ms
5.00 m
120 ms
Maximum Possible Protective Safety Field
Size
Basic Response Time
5.00 m
60 ms
5.00 m
120 ms
Multiple Sampling
Basic Response Time 60 ms Basic Response Time 120 ms
3 times
30 ms
60 ms
4 times
60 ms
120 ms
5 times
90 ms
180 ms
6 times
120 ms
240 ms
7 times
150 ms
300 ms
8 times
180 ms
360 ms
9 times
210 ms
420 ms
10 times
240 ms
480 ms
11 times
270 ms
540 ms
12 times
300 ms
600 ms
13 times
330 ms
660 ms
14 times
360 ms
720 ms
15 times
390 ms
780 ms
16 times
420 ms
840 ms
IMPORTANT
Ensure that the input electronics on
your machine or equipment do not
react to this test pulse and therefore
shut down the machine or equipment.
0.5 × basic response time
120 ms
120 ms
120 ms
Ca.
15 ms
OSSD1
OSSD2
t