Powerup
The DeviceNet™ Configuration Terminal is shipped so that when it is placed on
the network for the first time, it will automatically set its baud rate to that of the
traffic on the network, and then assign itself an unused network address. On
power up, the following screen is displayed:
Note that there is a 10-second powerup delay programmed at the factory. The
above screen will appear for at least 10 seconds on initial powerup. The powerup
delay can be modified in the Terminal Setup screen described in the following
section. Once the baud rate is determined and a network address has been set, the
terminal will display the Network Who screen, which displays a list of all devices
on the network.
Note:
To go directly to the Terminal Setup screen, press and hold the ESC key
during powerup.
IMPORTANT
If the terminal fails to enter the Network Who screen
after approximately 20 seconds, it is because it could
not determine the network baud rate due to lack of
traffic on the network. Pressing the
ESC key will allow
the user to enter the Terminal Setup screen so that a
fixed baud rate and network address can be set for the
terminal.
Baud = Fixed
baud rate
Auto =
AutoBauding
Actual baud
rate
Adrs = Fixed HIM
MacID
Auto = Auto
Addressing
Actual
terminal
address