Using adapter parameters, Using – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 30
30
Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Chapter 3
Configuring the Adapter
Using Adapter Parameters
By default, the adapter is configured to use a BOOTP server as the source for the
adapter IP address, subnet mask, and gateway address. To use adapter parameters
instead, you must first disable BOOTP with Parameter 36 - [BOOTP]. Then set
the associated adapter parameters as described in the following subsections.
Disable the BOOTP Feature
1.
Verify that the IP Address switches (
) are set to any
value other than 001…254 or 888.
The default setting is 999.
2.
Set the value of Parameter 36 - [BOOTP] to ‘0’ (Disabled).
3.
Reset the adapter by power cycling the drive or by using the HIM’s Reset
Device function located in the drive’s DIAGNOSTIC folder.
4.
Perform the steps in the following subsections to set the IP address, subnet
mask, and gateway address using adapter parameters.
Set the IP Address
1.
Verify that Parameter 36 - [BOOTP] is set to ‘0’ (Disabled).
2.
Set the value of Parameters 38 - [IP Addr Cfg 1] through 41 - [IP Addr
Cfg 4]
to a unique IP address.
3.
Reset the adapter by power cycling the drive or by using the HIM’s Reset
Device function located in the drive’s DIAGNOSTIC folder.
The ENET status indicator will be steady green or flashing green if the IP
address is correctly configured.
Set the Subnet Mask
1.
Verify that Parameter 36 - [BOOTP] is set to ‘0’ (Disabled).
Value
Setting
0
Disabled
1
Enabled (Default)
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit BOOTP
Disabled
0
0 << 1
Default = 0.0.0.0
255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Edit IP Addr Cfg 1
0
0 << 255
ESC
ENTER
Stopped
0.00 Hz
AUTO
F