Appendix d, Logic command word, Logic command/status words: powerflex – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 173: Series drives, Appendix
Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
173
Appendix
D
Logic Command/Status Words: PowerFlex
750-Series Drives
This appendix presents the definitions of the Logic Command and Logic Status
words that are used for PowerFlex 750-Series drives.
Logic Command Word
Logic Bits
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Command
Description
x
Normal Stop
0 = Not Normal Stop
1 = Normal Stop
x
Start
(1)
0 = Not Start
1 = Start
x
Jog 1
(2)
0 = Not Jog 1 (Par. 556)
1 = Jog 1
x
Clear Fault
(3)
0 = Not Clear Fault
1 = Clear Fault
x
x
Unipolar Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Manual
0 = Not Manual
1 = Manual
x
Reserved
x
x
Accel Time
00 = No Command
01 = Use Accel Time 1 (Par. 535)
10 = Use Accel Time 2 (Par. 536)
11 = Use Present Time
x
x
Decel Time
00 = No Command
01 = Use Decel Time 1 (Par. 537)
10 = Use Decel Time 2 (Par. 538)
11 = Use Present Time
x
Ref Select 1
000 = No Command
001 = Ref A Select (Par. 545)
010 = Ref B Select (Par. 550)
011 = Preset 3 (Par. 573)
100 = Preset 4 (Par. 574)
101 = Preset 5 (Par. 575)
110 = Preset 6 (Par. 576)
111 = Preset 7 (Par. 577)
x
Ref Select 2
x
Ref Select 3
x
Reserved
x
Coast Stop
0 = Not Coast to Stop
1 = Coast to Stop
x
Current Limit Stop
0 = Not Current Limit Stop
1 = Current Limit Stop
x
Run
(4)
0 = Not Run
1 = Run
x
Jog 2
(2)
0 = Not Jog 2 (Par. 557)
1 = Jog 2
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
(1)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition will start the drive.
(2)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog 1/Jog 2 condition will jog the drive. A transition to a ‘0’ will stop the drive.
(3)
To perform this command, the value must switch from ‘0’ to ‘1’.
(4)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Run condition will run the drive. A transition to a ‘0’ will stop the drive.