Appendix B
Adapter Parameters
46
47
48
49
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Sets the gateway address bytes for the adapter’s network address
when Parameter 36 - [BOOTP] is set to ‘0’ (Disabled), and the
IP Address switches (
) are not being used
(that is, switches set to any value other than 001…254 or 888).
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
50
[Net Rate Cfg]
Sets the speed and duplex network data rate at which the
adapter communicates. (Updates Parameter 51 - [Net Rate
Act] after a reset.)
Default:
0 = Autodetect
Values:
0 = Autodetect
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
Type:
Read/Write
Reset Required:
Yes
51
[Net Rate Act]
Displays the actual speed and duplex network data rate used by
the adapter.
Values:
0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
5 = Dup IP Addr
Type:
Read Only
52
[Web Enable]
Enables/disables the adapter’s web pages.
Default:
0 = Disabled
Values:
0 = Disabled
1 = Enabled
Type:
Read/Write
Reset Required:
Yes
53
[Web Features]
Enables/disables the web-configurable email notification
feature.
Default:
xxxx xxxx xxxx xxx1
Bit Values:
0 = Disabled
1 = Enabled
Type:
Read/Write
Reset Required:
No
Parameter
No.
Name and Description
Details
255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Bit
Definition
Not Use
d
Not Use
d
Not Use
d
Not Use
d
…
Not Use
d
Not Use
d
Not Use
d
Not Use
d
Not Use
d
Not Use
d
Not Use
d
E-
mai
l C
fg
Default
x
x
x
x
…
x
x
x
x
x
x
x
1
Bit
15 14 13 12 …
7
6
5
4
3
2
1