Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 129
Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
129
Adapter Parameters
Appendix B
35
[DLs To Net Act]
Displays the number of drive-to-controller Datalinks that the
controller is using based on the I/O connection opened by the
controller.
Minimum:
0
Maximum:
16
Type:
Read Only
36
[BOOTP]
Configures the adapter to use BOOTP so that you can set its IP
address, subnet mask, and gateway address with a BOOTP server.
When this parameter is disabled, you must use either the adapter
IP Address switches (
) or the adapter
parameters to set these addressing functions.
Default:
1 = Enabled
Values:
0 = Disabled
1 = Enabled
Type:
Read/Write
Reset Required:
Yes
37
[Net Addr Src]
Displays the source from which the adapter’s node address is
taken.
Values:
0 = Switches
1 = Parameters
2 = BOOTP
Type:
Read Only
38
39
40
41
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Sets the IP address bytes for the adapter’s network address when
Parameter 36 - [BOOTP] is set to ‘0’ (Disabled), and the IP
Address switches (
) are not being used (that
is, switches set to any value other than 001…254 or 888).
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
42
43
44
45
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Sets the subnet mask bytes for the adapter’s network address
when Parameter 36 - [BOOTP] is set to ‘0’ (Disabled), and the
IP Address switches (
) are not being used
(that is, switches set to any value other than 001…254 or 888).
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
Parameter
No.
Name and Description
Details
255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
Set with Octet Switch on
Drive Main Control Board
255.255.255.255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]