Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 112
![background image](/manuals/577306/112/background.png)
112
Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Chapter 7
Troubleshooting
Table 12 - Adapter Events
Code
Event
Description
Adapter Events
1
No Event
Text displayed in an empty event queue entry.
2
Device Power Up
Power was applied to the adapter.
3
Device Reset
The adapter was reset.
4
EEPROM CRC Error
The EEPROM checksum/CRC is incorrect, which limits adapter functionality. Default
parameter values must be loaded to clear this condition.
5
App Updated
The adapter application firmware was flash updated.
6
Boot Updated
The adapter boot firmware was flash updated.
7-24
Reserved
—
DPI Events
25
DPI Manual Reset
The adapter was reset.
26-28
Reserved
—
Network Events
29
Net Link Up
An network link was available for the adapter.
30
Net Link Down
The network link was removed from the adapter.
31
Net Dup Address
The adapter uses the same IP address as another device on the network.
32
Net Comm Fault
The adapter detected a communications fault on the network.
33
Net Sent Reset
The adapter received a reset from the network.
34
Net IO Close
An I/O connection from the network to the adapter was closed.
35
Net Idle Fault
The adapter received ‘idle’ packets from the network.
36
Net IO Open
An I/O connection from the network to the adapter has been opened.
37
Net IO Timeout
An I/O connection from the network to the adapter has timed out.
38
Net IO Size Err
The adapter received an incorrectly sized I/O packet.
39
PCCC IO Close
The device sending PCCC Control messages to the adapter has set the PCCC Control
Timeout to zero.
40
PCCC IO Open
The adapter has begun receiving PCCC Control messages (the PCCC Control Timeout
was previously set to a non-zero value).
41
PCCC IO Timeout
The adapter has not received a PCCC Control message for longer than the PCCC Control
Timeout.
42
Msg Ctrl Open
The timeout attribute in either the CIP Register or Assembly object was written with a
non-zero value, allowing control messages to be sent to the adapter.
43
Msg Ctrl Close
The timeout attribute in either the CIP Register or Assembly object was written with a
zero value, disallowing control messages to be sent to the adapter.
44
Msg Ctrl Timeout
The timeout attribute in either the CIP Register or Assembly object elapsed between
accesses of those objects.
45
Peer IO Open
The adapter received the first Peer I/O message.
46
Peer IO Timeout
The adapter has not received a Peer I/O message for longer than the Peer I/O Timeout.
47-54
Reserved
—
55
BOOTP Response
The adapter received a response to its BOOTP request.
56
E-mail Failed
The adapter encountered an error attempting to send a requested e-mail message.
57
Option Card Flt
The adapter experienced a generic fault condition (drive only).
58
Module Defaulted
The adapter has been set to defaults.